MAGNUM VERSION 8 MANUAL REVISION 3.1
133
If you are going to manually assign the IP Address, Subnet Mask, and Default Gateway.
Press the Menu key, select Serv Tools, and then press the Enter key.
Select Ethernet Network then press Enter.
Set “DHCP Enabled” to NO.
Set the “IP Address”.
Set the “Subnet Mask”.
Set “Default Gateway”.
If you are going to let your network assign the IP Address, Subnet Mask, and Default Gateway:
Press the Menu key, select Serv Tools, and then press the Enter key.
Select Ethernet Network then press Enter.
Set “DHCP Enabled” to YES.
Connect the MCS-Magnum to the network and power up the board.
Johnson N2
11.11.4.
The N2 address can be verified and changed (with the proper authorization code) from the keypad/LCD.
Press the Menu key, select Serv Tools, and then press the Enter key.
Select RS485 Network then press Enter.
Select Protocol then press Enter. Change the protocol to N2.
Select address then press Enter. Change the address then press Enter.
Select Baud then press Enter. Set the baud rate then press Enter.
Connect the communication wires to the TX RS485 three-position terminal located above the Ethernet
connector.